• leaking toilet
  • Small hole in copper pipe
  • Leaking tap
  • Tap washer replacement 1
  • Tap washer replacement 2
  • Tap washer replacement 3
  • Balancing a central heating system
  • Bleeding a radiator
  • Corrosion prevention in heating systems
  • Leaks in central heating systems
  • Problem solving central heating 1
  • Problem solving central heating 2

  • How to Repair a Leaking Toilet:

    Determine what is leaking by checking possible sources of water leaks in the toilet.

    Start by checking if there is water collecting on the floor close to the toilet valve. If there is, check the valve to see if it is the source of the leakage. If the valve is leaking, tighten it using two wrenches. If the leaking doesn’t stop, replace the valve with a new one. But before doing this, make sure you shut off the main water source valve to prevent flooding.

    If the leak doesn’t come from the toilet valve, check the hose that passes the water from the source to the tank for any breakage, tear, or kinks. If there’s none of these, tighten the hose using channel locks. If it doesn’t stop the leaking, tighten the nut that’s holding the fill valve.

    If the above step doesn’t stop the leak, the gaskets are defective and you need to replace them. Shut off the water first then drain the tank. Undo the hose, open the tank lid, hold the fill valve and untighten the nut on the bottom of the tank. Replace the gaskets with new ones.

    f the water is leaking between the tank and toilet bowl, then most likely the seal between them is not properly set or worn out. The seal may need to be replaced. Make sure to drain the water from the tank and shut off the valve first. Unscrew the bolts that are holding the tank and toilet bowl together. Pull out the tank upwards and inspect the seal. If it’s broken, replace it. After replacement, put the components back together.

    If the toilet is leaking on the bottom base, most likely the wax ring may be worn out or the base is loose. First thing you might want to try is tighten the two screws that are holding the toilet base to the floor. If that doesn’t help, you need to replace the wax ring. Make sure the water tank is empty of water first. Suck in all the water in the toilet bowl using a wet vacuum or anything you can use to drain the water out. Unscrew the two bolts on the bottom of the base. Lift up the toilet bowl and flip it sideways. Clean the existing wax off the toilet and the drain. Put the new wax ring into the drain hole. Put two bolts in their holding space. Lift the toilet bowl over the wax ring making sure not to move them. Set the toilet in place making sure the bolts are in their proper location. Wiggle the toilet base to seal it in properly. Tighten up the bolts, close up the cover, then turn the water back on.

    If you still can’t able to fix the leak, it’s best to call a professional to do the job for you.
     


    How to Repair a Small Hole in Copper Pipe:

    It is not always practical to carry out a permanent repair immediately on a leaking pipe.
    A temporary repair can be effected until a permanent repair is possible. Isolate the water supply to the pipe concerned and drain it down.
    Take a piece of garden hose of sufficient diameter to go round the pipe. Cut it lengthways and place it over the damage. Fasten with at least three jubilee clips. One in the centre and one at either end. By tightening these sufficiently, you should be able to seal the hose against the pipe so that no further water escapes.

    Permanent repair:
    Whilst a temporary repair can overcome the immediate problem, it is always advisable to carry out a permanent solution as soon as possible.
    Drain the affected pipework. Cut out the damaged section and fit a new length of pipe with compression or solder fittings at each end.


    Leaking tap:

    Older style taps are fitted with a gland nut holding in watertight packing around the spindle. These taps may leak between the spindle and the cover if the gland nut has become loose. To cure a similar problem on modern taps, or to cure a tap which drips, refer to washer replacement

    Tightening the tap gland nut:
    Undo the small screw holding the cross head in place (this may be hiding under a plastic cover in the top of the tap) and remove it.
    Undo the top cover of the tap by unscrewing. This may be a metal type with a hexagonal base, in which case you should wrap some cloth around it before undoing with a spanner. The cloth will prevent it being scratched. Take care to prevent the tap itself from turning whilst doing this.
    With the cover removed, tighten the gland nut at the base of the spindle with a spanner.
    Hold the tap (wrapped in a rag) with a pipe wrench to prevent it turning.
    Before reassembling, check that the nut is not so tight as to make it difficult to turn on the tap. This can be done by replacing the cross head temporarily without the fixing screw and testing the tap.
    Repacking the tap gland:
    If this fails to cure the problem, turn off the water, remove the gland nut and repack the gland. Remove the old packing with a small screwdriver. Replace it with specially produced packing or, if you are unable to get hold of this, use string coated with petroleum jelly. Reassemble and test the function of the tap.


    Tap washer replacement 1:

    Locating the washer
    Close off the water supply to the tap and open the tap to drain excess water.
    Put the plug in the waste outlet - not to stop loss of water, but to safeguard against losing any of the tap components when dismantling it.
    Remove the top cover of the tap. This may be a metal type with a hexagonal base, in which case you should wrap some cloth around it before undoing with a spanner. The cloth will prevent it being scratched. Hold the tap itself to prevent it turning.
    Some taps have a moulded plastic cover held in place with a small screw located in its top (sometimes under a plastic insert, which will need to be gently prised out with a thin bladed screwdriver).

    Undoing the tap
    Once the cover is removed, undo the top section of the tap by turning the hexagonal nut next to the base with a spanner.
    Hold the tap itself (wrapped in a rag) using a pipe wrench to prevent it turning.
    Lift the top section out of the tap.

    Replacing the washer
    On the underside of this will be the washer retained by a small nut, which should be undone, or a button.
    Remove the old washer and replace with a new one. Make sure that pieces of the old washer are not left in the seat of the tap before finally reassembling it and switching the water back on.


    Tap washer replacement 2:

    Reverse pressure tap
    This is a rather old form of tap but it is quite possible to change its washer if needs be using readily available replacements.
    A valve inside the tap enables the washer may be replaced without the need to switch off the water supply.
    Wrap a cloth around the hexagonal nut above the nozzle and hold it with a spanner. Unscrew the nozzle with the other hand.
    Tap (no pun intended) the nozzle on a block of wood to free the finned section inside. Remove and replace the combined washer jumper.
    Reassemble the tap and test.

    Mixer tap spout
    If leakage occurs from the base of the spout, the likely cause is a worn seal.
    Turn off both taps but not the main supply to them.
    Unscrew or lift up the retaining shroud.
    Lift the spout up carefully.
    On some models, the spout is held in place with a retaining screw, which should be undone.
    Remove and replace the worn seal, which is usually an "O" ring type – like a little rubber ring sitting in the groove on the assembly.
    Be sure not to damage or stretch the "O" ring when refitting your spout. A little silicone lubricant may be used to ease reassembly.


    Tap washer replacement 3:

    Mixer tap valves
    Modern mixer tap valves now have "O" rings in place of the old gland packing.
    To replace these, turn off the water supply to both hot and cold, remove the cover piece and the circlip holding the stem in place. To do this, place the blade of a screwdriver between the ends of the clip and twist – be prepared to catch the clip. Once released, it has an extraordinary ability to vanish!
    Undo the mechanism and remove the assembly.
    Remove and replace the "O" rings. Take care not to damage them. A little silicone lubricant may be used to ease reassembly.


    Balancing a central heating system:

    To ensure an even distribution of the hot water to the radiators in a system you’ll need to do what’s known as balancing the system. Because the water is pumped via a pipe, and branches to feed each radiator, the ones at the beginning of the ‘run’ tend to get more than their fair share.
    The way to do this is by using the lockshield valve on each to regulate the flow of water to the radiator. By partial closing of these valves the radiators nearest the pump can be restricted more than those further away.
    The best way to get this right is by using radiator thermometers, which can simply be clipped to the flow and return pipe at either end, and measuring the difference. You won't often see a plumber using these though - experience enables them to adjust the valves without measuring the temperature.
    Remember, the pipe to each radiator is a branch from the main flow pipe. Near the furthest radiator, the main flow pipe turns back towards the boiler and becomes the return pipe. The pipe from each radiator then feeds back into this.
    The water does not go into the first radiator then out and on to the next etc. It actually flows from one main pipe feeding all of them, and then flows back out into the return coming back from all of them.
    Turn the heating off well in advance of wishing to balance the system, so that the water has a chance to cool right down. Each radiator has a control valve – the one you use to turn it on or off, and a lockshield valve – the one with a cover which you don’t normally turn. To open or close this lockshield valve, you need to remove the cover and use a pair of pliers. Open both valves on all the radiators.
    Now, turn the heating back on and go to the first radiator. You are going to adjust them in the order in which they are served, so if you don’t know this, make a note of the order in which they heat up.
    Fit the radiator thermometers to the flow and return. Turn off the lockshield valve then open it gradually again until the difference between the two thermometers is about 20 degrees Farenheight.
    Move on to the second radiator on the system and do the same. If you repeat this for all of them in order, you should have a perfectly balanced system so that all radiators heat up efficiently. You may find the last one will need the lockshield valve fully open.
     


    Bleeding a radiator:

    For sealed systems, seek the services of a professional heating engineer
    Cold radiator
    If the top section of a radiator is cold when the heating is on, it is usually an indication that air has got into the system somewhere and has become trapped. Air in a radiator will rise to the top forming a pocket stopping the hot water from getting to that part.This can be released by bleeding the radiator,, but remember to turn the heating off first.
    When air is bled or released from an open vented system, the water in the system will be topped up by the feed and expansion tank.
    If a radiator in a sealed system needs bleeding the pressure in the system will be reduced. The system will, therefore, needed to be toped up. However, sealed systems are different from open vented ones and have no feed and expansion tank. The instruction manual for your system may have details of how to top up the system. If not, or if you have any doubts at all, contact a suitably qualified heating engineer.

    Bleed the radiator
    You will need a radiator key and an old rag. Radiator keys are readily available from DIY stores and ironmongers. Armed with the rag beneath, use the radiator key to slacken the air bleed valve which is at one end towards the top of the radiator.
    There will be a hissing sound as the air comes out. As soon as water begins to flow, close the vent again and wipe away any water.
    Take care not to get scalded – the water may be pretty hot.
    The heating can then be switched back on.

    Air release valve
    Some systems have an automatic air release valve fitted. This usually has a small red top which should be slack to enable the air to escape.
    Radiators should not need frequent ‘bleeding’. If they do, air is getting in and this should be sorted out by a professional heating engineer.


    Corrosion prevention in heating systems:

    A few simple precautions can avoid your system having problems like sludge build up and pinhole leaks.

    Cause of corrosion:
    Air getting into the system actually speeds up deterioration as oxygen is one of the essential requirements for corrosion.
    You’ll know if air is getting in because the radiators will need bleeding to remove the air on a frequent basis.
    Where the air gets in though is another matter. It can enter through a number of routes, but the most common are through the feed and expansion cistern in the loft, the vent pipe which hangs over it or a leaking joint beside the pump.
    Unfortunately, whilst it is possible to identify these, it is usually a job for a professional heating engineer to put it right.

    Testing for corrosion:
    It’s a good idea to add a corrosion inhibitor to reduce the gradual deterioration of the system. Test a sample of water from your system each year to see how corrosive it is. Place the sample in an old jam jar and put a shiny steel nail in it.
    Remember not to use a galvanised nail or the test won’t work.
    Put the lid back on and leave the jar for a week or so. If the water has turned orange and the nail is rusty, the water has too much oxygen and will be corroding the inside of your system in the same way. You’ll therefore need to put an additive into the system to reduce this.

    Adding corrosion inhibitor:
    Read the manufacturer’s instructions carefully
    and add the appropriate amount of the anti corrosion liquid. With an open vent system, this is done by adding to the feed and expansion cistern.
    For a sealed system, you can buy a cartridge of inhibitor which can be injected in via the air bleed valve on a radiator -
    again, you should carefully follow the manufacturer's instructions for this.


    Leaks in central heating systems:
    For sealed systems, seek the services of a professional heating engineer

    Joints in pipework:
    Soldered joints which have sprung a leak will need to be replaced. Drain the system and replace the joint by following the section on soldered joints.
    Compression joint leaks can sometimes be cured by a slight tightening of the nut.
    Remember to hold the other nut with a spanner or wrench to prevent pulling the joint from the pipe.
    Tighten the leaking side a small amount and no more than a quarter turn. More than this and you’ll damage the joint. If this is not successful, you’ll need to drain down the system and refit the joint. Refer to compression fittings in the plumbing section.

    Radiator:
    Radiators can develop pinholes. This is caused by corrosion due to sludge or excessive air getting into the system. The air actually promotes corrosion. The only satisfactory cure is to remove the radiator and fit a new one. Be sure however to flush the system through and identify whether air is getting into the system.
    Failure to resolve the cause may mean you’ll get very used to replacing radiators!

    Valve connections:
    If the valve leaks where it connects to the pipework, you will need to repair the joint. The system will need to be drained down and the joint redone. This is a compression type joint and relies upon a metal collar known as an olive to make the seal when the nut is tightened. For details on how to make this type of connection see compression fittings in the plumbing section.
    If the leak is the other side of the valve where it goes off to the radiator, you can turn off both valves and drain just the radiator in question. Whilst you won’t need to remove the radiator, you’ll find details on emptying it in the removing a radiator section. Undo the connection, and wind a length of PTFE tape around the joint before reassembling and you’ll find that this will help to seal the thread and stop any leaks. Open the air vent and then open just the flow valve. Allow the radiator to fill and close the air bleed valve when water begins to come out. Now open the return valve.

    Radiator connector:
    Follow the same procedure above to empty the radiator. Disconnect the radiator from the valve first, then use a large Allen key inserted in the end to undo the radiator connector. Then clean the thread and wrap a length of PTFE tape around it. Refit the connector to the radiator doing it up with the Allen key, and reconnect the valve.

    Air bleed valve:
    Partially drain the radiator so that the water level inside is at least below the level of the air bleed valve. Using an Allen key inserted into the valve, you can undo and remove it. Clean the thread and wrap a little PTFE tape around it before reinserting and tightening it back up. Refill the radiator.

    Valve body:
    The gland nut at the base of the spindle of a valve sometimes works loose.
    Holding the valve assembly with a pipe wrench to prevent it being pulled from the pipework, use a spanner to tighten the nut a little. If this doesn’t do the trick, it indicates that the gland packing has become worn. Turn off both valves and undo the gland nut. Using a length of special gland packing, wind a few turns around the base of the spindle and pack it in tightly using a small screwdriver. Replace and retighten the gland nut. Open one valve at a time and check again for leaks.


    Problem solving central heating 1:

    For problems relating to sealed systems, seek the services of a professional heating engineer

    Cold top section of radiator:
    This is usually an indication that air has got into the system somewhere and has become trapped. Air in a radiator will rise to the top forming a pocket stopping the hot water from getting to that part. This can be released, but remember to turn the heating off first. Now, armed with a rag beneath, use a radiator key to slacken the air bleed valve which is at one end towards the top of the radiator. There will be a hissing sound as the air comes out. As soon as water begins to flow, close the vent again and wipe away any water.
    Take care not to get scalded – the water may be pretty hot.
    The heating can then be switched back on.
    Some systems have an automatic air release valve fitted. This usually has a small red top which should be slack to enable the air to escape.
    Radiators should not need frequent ‘bleeding’. If they do, air is getting in and this should be sorted out by a professional heating installer

    Cold bottom section of radiator:
    This is a sign of rust and sludge build up which is sitting in the bottom of the radiator. Following the guides on removing and refitting a radiator, take the radiator outside and flush it through with a hosepipe. If you have the radiator standing on end, you should be able to flush out most of the sludge.
    Remember to carry the radiator upside down so you don't get sludge dripping on to your carpet.
    With an open vent system, you may also consider using a proprietary heating system sludge remover. This will mean adding it to the feed and expansion tank and, a few days later, emptying and refilling the system.
    Follow the manufacturer’s instructions.

    Upstairs radiators cold:
    This is most often an indication that the feed and expansion cistern in the loft has run dry.
    This should not happen and indicates another problem which needs to be sorted.
    It’s probable that the ball valve is not operating correctly. It may have jammed or be obstructed. Clear any obstruction or replace worn parts. Remember when refilling and adjusting the ball valve that there must be enough room for the water to expand when the system heats up. Therefore, when the system is cold, there should be just enough water to make the ball to float and switch off the water coming in.

    Downstairs radiators cold:
    This is an indication that the pump has packed up. Have it tested and, if necessary, replaced.

    All radiators cold or not very warm:
    This again is an indication of the build up of rust and sludge. See ‘Cold bottom section’ above.
    Radiators cooler in one area of the house
    This tells you that the radiators are not properly balanced. The nearest radiators to the boiler are taking more than their share of the hot water from the system. See page on balancing the system.

    Warm radiators upstairs when the heating is off, and hot water is on:
    If this happens, it is probably because the check valve on a gravity fed system has failed. In a gravity fed system, the hot water cylinder is heated by water from the boiler which flows due to the gravity and not a pump. To prevent the water also heating the radiators when the heating is off, a check valve is fitted. If this has failed, the radiators upstairs will begin to receive some of the heat.
    The valve will need to be replaced by a heating engineer.

    No heating or hot water:
    Make sure that the power supply is on and that a fuse hasn’t blown. Remember, if a fuse has blown, you should always rectify the cause first.
    As always, take great care with any electrical inspection or work. See electrics safety
    Check that the gas or oil supply has not been turned off inadvertently.
    In the case of oil, check that you actually have some oil in the tank by reading the gauge.
    Check that the programmer is in the on position and that the thermostats are turned up high enough.
    Check that the pump is running.
    If not, get a heating engineer in to investigate.
    Check that the pilot light is lit.
    If it isn't, follow the details for relighting in the boiler manual.
    If none of these solve the problem, it’s time to call in a heating engineer.

    Feed and expansion tank overflowing:
    If the ball valve is not closing off the water supply properly, the cistern will continue to fill and water will come out from the overflow pipe. The usual cause is either a poorly adjusted valve or a worn washer. These can both be remedied in a similar fashion to the ball valve of the cold water storage tank.


    Problem solving central heating 2:

    Noisy heating:
    A number of different things may cause noise problems with a heating system.

    Water gurgling:
    This is a sign that air has got into the system. This can be released by bleeding air from the radiators.
    but remember to turn the heating off first
    Now, armed with a rag beneath, use a radiator key to slacken the air bleed valve which is sited at one end towards the top of the radiator. There will be a hissing sound as the air comes out. As soon as water begins to flow, close the valve again and wipe away any water.
    Take care not to get scalded – the water may be pretty hot.
    The heating can then be switched back on.
    Some systems have an automatic air release valve fitted. This usually has a small red top which should be slack to enable the air to escape.
    Radiators should not need frequent ‘bleeding’.
    If they do, air is getting in and this should be sorted out by a professional heating installer.

    Humming:
    The pump which sends the water around the system may be set too fast. In this case , try turning it down to a lower setting. Pumps can also cause this noise in the pipework through vibration of the pipes. This can be eliminated by mounting the pump on special brackets which absorb the vibration rather than transferring it to the pipes. Finally, the problem can arise where undersized pipes have been installed.
    Check this out with a heating engineer.

    Knocks and creaking:
    Everywhere that pipes pass through other materials like floor joists or walls, there is a possibility that they will rub when they expand or contract unless enough space has been left. If you can identify where the noise comes from, investigate the pipework in the area to see where it is rubbing. Rubbing against floor joists where the notch out is too narrow to allow a little movement, is a common cause. This can easily be widened by cutting an extra slither away from one side with a saw and chiselling away the waste.
    Take care not to damage the pipe and do not deepen the notch as this weakens the joist.
    You can also pack a bit of fibreglass insulation around them to cushion the rubbing. This packing can also help where pipes come up through floorboards.
    Sometimes pipes running beneath the floorboards have not been supported properly. If you find pipework which has a lot of free movement - for example where they run parallel to the joists - they will need to be secured. Fit a small batten, screwed between the joists, and use pipe clips to retain the pipes.

    Noisy boiler:
    This may be caused by sludge and scale inside the boiler which results in some areas heating up more than others. The result is usually intermittent banging caused by pockets of steam. The same sludge build up can also restrict the flow of water which will result in noisiness. Air in the boiler may also cause noises.
    With any of these, it is recommended that you seek the services of a professional heating engineer.
    There may be a lack of water. Check the feed and expansion tank. If it is not topping up when the ball valve is opened, there may be a frozen pipe, air lock, or the mains water may have been switched off.